Zalecane wartości maksymalnych dopuszczalnych jednostkowych strat mocy cieplnej q [W/m] – ciepłownictwo
Średnica nominalna przewodu [mm] |
Maksymalna obliczeniowa temperatura nośnika ciepła [°C] | |||||||
---|---|---|---|---|---|---|---|---|
50 | 70 | 90 | 110 | 130 | 150 | 180 | 200 | |
32 | 13 | 20 | 26 | 30 | 34 | 40 | 49 | 56 |
40 | 14 | 22 | 28 | 32 | 36 | 43 | 51 | 59 |
50 | 15 | 24 | 31 | 36 | 41 | 46 | 55 | 63 |
65 | 16 | 26 | 34 | 40 | 46 | 51 | 62 | 71 |
80 | 17 | 29 | 36 | 42 | 47 | 53 | 64 | 75 |
100 | 19 | 33 | 39 | 47 | 52 | 60 | 71 | 83 |
125 | 20 | 35 | 41 | 50 | 55 | 65 | 77 | 90 |
150 | 22 | 39 | 46 | 54 | 63 | 71 | 85 | 96 |
200 | 24 | 41 | 52 | 63 | 71 | 81 | 97 | 113 |
250 | 29 | 48 | 60 | 73 | 83 | 94 | 112 | 131 |
300 | 30 | 55 | 65 | 76 | 88 | 102 | 122 | 142 |
350 | 32 | 57 | 68 | 82 | 94 | 109 | 129 | 152 |
400 | 36 | 59 | 69 | 84 | 97 | 110 | 134 | 160 |
450 | 39 | 63 | 74 | 90 | 104 | 121 | 146 | 169 |
500 | 40 | 65 | 77 | 93 | 106 | 125 | 151 | 176 |